z UNIVERSAL OUTPUT
z SELF-POWERED
z EASILY ADJUSTABLE SETPOINT
z FIXED OR SPLIT-CORE CASE
GENERAL DESCRIPTION
CTS Series Transducers are self-powered, solid-state current-operated
switches that trigger when the current level sensed through the aperature
exceeds the adjusted setpoint. The solid state output contacts can switch AC or
DC; this “universal” output makes them well suited for application in
automation systems.
CTS Series Current Operated Switches combine a current transformer, signal
conditioner and limit alarm into a single package for use in status monitoring or
proof of operation applications. Offering an extended setpoint range of 1-150 A
and universal, solid-state outputs, the self-powered CTS can be tailored to
provide accurate and dependable digital indication of over-current conditions
across a broad range of applications. Available in solid-core enclosure styles or
in a split-core case to maximize ease of installation.
SAFETY SUMMARY
All safety related regulations, local codes and instructions that appear in the
literature or on equipment must be observed to ensure personal safety and to
prevent damage to either the instrument or equipment connected to it. If
equipment is used in a manner not specified by the manufacturer, the protection
provided by the equipment may be impaired.
Do not use this unit to directly command motors, valves, or other actuators
not equipped with safeguards. To do so, can be potentially harmful to persons or
equipment in the event of a fault to the unit.
SPECIFICATIONS
1. POWER SUPPLY: None - self powered
2. OUTPUT: Magnetically isolated normally open solid-state switch
3. OUTPUT RATING: 0.15A, 240 VAC/VDC
4. OFF STATE LEAKAGE: <10 μA
5. RESPONSE TIME: 120 msec
6. HYSTERESIS: Approx 5% of Setpoint
7. SETPOINT RANGES AND MAXIMUM AMPS:
8. SETPOINT ADJUST: 4 Turn potentiometer (CTSS)
15 Turn Potentiometer (CTSF)
9. FREQUENCY RANGE: 6-100 Hz
10. ISOLATION VOLTAGE: UL Listed to 1,270 VAC. Tested to 5,000 VAC
11. CASE: UL 94V-0 Flammability rated thermoplastic
12. ENVIRONMENTAL: -58 to 149 °F (-50 to 65 °C)
0-95% RH, non-condensing
13. TORQUE RATINGS: 5 in-lbs
14. LISTING: UL 508 Industrial Control Equipment, CSA C22.2 No. 14-M95,
and CE Certified.
MODEL CTS - AC CURRENT OPERATED SWITCH
Bulletin No. CTS- A
Drawing No. LP0651
Released 4/08
Tel +1 (717) 767-6511
Fax +1 (717) 764-0839
www.redlion.net
C
US LISTED
U
L
R
IND. CONT. EQ.
5T44
0.85
(21.6)
0.85
(21.6)
3.53
(89.7)
2.40
(61)
3.04
(77.2)
Ø 0.19
(4.8)
2.25
(57.2)
1.19
(30.2)
DIMENSIONS In inches (mm)
SPLIT-CORE
3.50
(88.9)
3.03
(77.0)
0.93
(23.6)
Ø 0.19
(4.8)
2.40
(61.0)
2.18
(55.4)
Ø 0.74
(19)
DIMENSIONS In inches (mm)
FIXED-CORE
1000 A250 A 400 A
1000 A150 A 400 ASplit-Core: 1.75 - 150 A
1000 A150 A 400 AFixed-Core: 1 - 150 ACTSF
CTSS
CTSG
1 secContinuous
6 sec
MAXIMUM INPUT AMPS
SETPOINT RANGEMODEL
CAUTION: Risk of Danger.
Read complete instructions prior to
installation and operation of the unit.
CAUTION: Risk of electric shock.
Fixed-Core Go/No Go:
0.75 A max