Red-lion PAX2D User Manual Page 31

  • Download
  • Add to my manuals
  • Print
  • Page
    / 36
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 30
31
TROUBLESHOOTING
PROBLEM REMEDIES
No Display At Power-Up Check power level and power connections.
No Display After Power-Up
Check Display Module: d-LEU, d-Cont, and LINE 1 program settings.
Program Locked-Out
Check for Active User Input, programmed for PLOC. Deactivate User Input.
Enter proper access code at COdE 0 prompt. (Universal access code = 222)
No Line 1 Display Check program settings for Line 1 Display Value Select/Enable. Confirm at least one Line 1 Display
Value is enabled (YES).
No Line 2 Display Check program settings for Line 2 Value Access. Confirm at least one Line 2 Parameter Value is enabled
in Main Display Loop (d-rEAd, d-rSt, d-Entr).
No Line 1 Units Mnemonic Display Check program settings for Line 1 Units Mnemonic(s).
Display of OUEror UndEr Value exceeds Display capacity of the meter. See General Meter Specifications.
Incorrect Display Value or Not Counting Check Input wiring, DIP switch setting, Input programming, Scale Factor calculation, Input signal level,
User Input Logic setting, lower input signal frequency.
User Input Not Functioning Check User Input wiring, User Logic setting, User Function settings, User Input being used as a signal
input in dual count modes (see Counter Operating Modes).
Modules or Parameters Not Accessible Check for corresponding plug-in option card.
Verify parameter is valid in regard to previous program settings.
Error Code: ErrKEY Keypad is active at power up. Check for depressed or stuck keypad. Press any key to clear Error Code.
Error Code: EE PAr
Error Code: EE Pdn
Parameter Data Checksum Error. Press any key to clear Error Code, verify all program settings and cycle
power. Contact factory if Error Code returns at next power-up.
Error Code: ErrPro Parameter Data Validation Error. Press any key to clear Error Code, verify all program settings and cycle
power. Contact factory if Error Code returns at next power-up.
Error Code: EE Lin Linear Output Card Data Validation Error. Press any key to clear Error Code and cycle power. If Error
Code returns at next power-up, replace Linear Option Card or contact factory.
PARAMETER VALUE CHART Programmer ________________ Date ________
PAX2D Meter# _____________ Security Code ________
INPUt INPUT SETUP PARAMETERS
COUNt Counter Parameters
DISPLAY PARAMETER USER SETTING
COUNTER A PARAMETERS
Cnt A
Counter A Operating Mode
dEC Pt
Counter A Decimal Position
SC FAC
Counter A Scale Factor
SCALEr
Counter A Scale Multipiler
RESEt
Counter A Reset Action
Cnt Ld
Counter A Count Load Value
R P-UP
Counter A Reset At Power-Up
PS Out
Prescaler Output Enable
PS SCL
Prescaler Scale Value
COUNTER B PARAMETERS
Cnt b
Counter B Operating Mode
dEC Pt
Counter B Decimal Position
SC FAC
Counter B Scale Factor
SCALEr
Counter B Scale Multipiler
RESEt
Counter B Reset Action
Cnt Ld
Counter B Count Load Value
R P-UP
Counter B Reset At Power-Up
COUNTER C PARAMETERS
Cnt C
Counter C Operating Mode
dEC Pt
Counter C Decimal Position
SC FAC
Counter C Scale Factor
SCALEr
Counter C Scale Multipiler
RESEt
Counter C Reset Action
Cnt Ld
Counter C Count Load Value
R P-UP
Counter C Reset At Power-Up
RAtE Rate Parameters
DISPLAY PARAMETER USER SETTING
RATE A PARAMETERS
RAtE A
Rate A Enable
DISPLAY PARAMETER USER SETTING
dEC Pt
Rate A Decimal Position
SC PtS
Rate A Scaling Points
RAxdSP 1
Rate A Scaling Point 1 Display
RA INP 1
Rate A Scaling Point 1 Input
RAxdSP 2
Rate A Scaling Point 2 Display
RA INP 2
Rate A Scaling Point 2 Input
RAxdSP 3
Rate A Scaling Point 3 Display
RA INP 3
Rate A Scaling Point 3 Input
RAxdSP 4
Rate A Scaling Point 4 Display
RA INP 4
Rate A Scaling Point 4 Input
RAxdSP 5
Rate A Scaling Point 5 Display
RA INP 5
Rate A Scaling Point 5 Input
RAxdSP 6
Rate A Scaling Point 6 Display
RA INP 6
Rate A Scaling Point 6 Input
RAxdSP 7
Rate A Scaling Point 7 Display
RA INP 7
Rate A Scaling Point 7 Input
RAxdSP 8
Rate A Scaling Point 8 Display
RA INP 8
Rate A Scaling Point 8 Input
RAxdSP 9
Rate A Scaling Point 9 Display
RA INP 9
Rate A Scaling Point 9 Input
RAxdSP 10
Rate A Scaling Point 10 Display
RA INP 10
Rate A Scaling Point 10 Input
ROUNd
Rate A Display Rounding
LO-CUt
Rate A Low Cut-Out
RATE B PARAMETERS
RAtE b
Rate B Enable
dEC Pt
Rate B Decimal Position
SC PtS
Rate B Scaling Points
RbxdSP 1
Rate B Scaling Point 1 Display
Rb INP 1
Rate B Scaling Point 1 Input
RbxdSP 2
Rate B Scaling Point 2 Display
Rb INP 2
Rate B Scaling Point 2 Input
Page view 30
1 2 ... 26 27 28 29 30 31 32 33 34 35 36

Comments to this Manuals

No comments