4.1 POWER WIRING
1
2
AC/DC
AC/DC
4.2 INPUT SIGNAL WIRING
1
2
AC/DC
AC/DC
+
-
1
2
AC/DC
AC/DC
+
-
OR
AC Power
DC Power
CAUTION: Sensor input common is NOT isolated from user input common. In order to preserve the safety of the meter application, the sensor input
common must be suitably isolated from hazardous live earth referenced voltage; or input common must be at protective earth ground potential. If not,
hazardous voltage may be present at the User Inputs and User Input Common terminals. Appropriate considerations must then be given to the potential
of the user input common with respect to earth ground; and the common of the isolated plug-in cards with respect to input common.
345
MAGNETIC PICKUP
6
+18VOUT
COMM
INPUT A
INPUT B
3
1
2
ON
63 4 5
to 2.5 mA MAX.
Resistor to limit current
AC
+18VOUT
COMM
INPUT A
INPUT B
3
2
1
ON
43 5 6
2.2K
COMM
+18V
OUT
INPUT B
INPUT A
2
1
3
ON
NPN O.C.
3 4 5 6
COMM
+18V
OUT
INPUT A
INPUT B
1
2
3
ON
PNP O.C.
3 4 5 6
+18VOUT
COMM
INPUT A
INPUT B
2
1
3
ON
ON
4
2
3
1
3 5 6
+5V
COMM
DIODE
+18VOUT
COMM
INPUT B
INPUT A
3 4 5 6
INPUT A
INPUT B
COMM
+18V
OUT
2
1
3
ON
63 4 5
INPUT A
INPUT B
+18V
OUT
COMM
1
2
3
ON
3 4 5 6
INPUT A
INPUT B
+18V
OUT
COMM
2
1
3
ON
AC Inputs From Tach Generators, Etc.
Input A
Two Wire Proximity, Current Source
Input A
Magnetic Pickup
Input A
Current Sourcing Output
Input A
Interfacing With TTL
Input A
Current Sinking Output
Input A
Switch or Isolated Transistor; Current Sink
Input A
Switch or Isolated Transistor; Current Source
Input A
Emitter Follower; Current Source
Input A
63 4 5
NPN O.C.
+18VOUT
COMM
INPUT A
INPUT B
4
1
2
3
6
5
ON
3 4 5 6
NPN O.C.
Count A
8 9
NPN O.C.
Count B
+18V
OUT
COMM
INPUT A
INPUT B
3
2
1
ON
4
5
6
USER 1
USER 2
Quad; Current Sink Output
Single
Counter A
Counter A &
Counter B
Dual Quad/Quad; Current Sink Output
If you are wiring Input B, connect signal to Terminal 6 instead of 5, and set DIP switches 4, 5, and 6 to the positions shown for 1, 2, and 3.
Shaded areas not recommended for counting applications.
63 4 5
NPN O.C.
NPN O.C.
8
Rate
Count
+18VOUT
COMM
USER 1
INPUT A
INPUT B
4
1
2
3
6
5
ON
Dual Quad/Count; Current Sink Output
Counter A
& Rate B
If using single Counter B, then wire signal to 6,
and Quad/Direction to 9. Set switches as shown.
The power supplied to the meter shall employ a 15 Amp UL approved circuit breaker for AC input and a 1 Amp, 250 V UL approved fuse for DC input. It shall be
easily accessible and marked as a disconnecting device to the installed unit. This device is not directly intended for connection to the mains without a reliable means
to reduce transient over-voltages to 1500 V.