The Programming Data For The Example:
Input Module 1 (1-IN)
Mnemonic Value Description
InPt P1rH User input is programmed for run/pause
operation
Alarm Module 4 (4-AL)
Mnemonic Value Description
Act 1 P-Ev Program alarm 1 for timed event output
Act 2 P-Ev Program alarm 2 for timed event output
Profile Module 8 (8-Pr)
Mnemonic Value Description
P1CC 1 Cycle profile once after started
P1Ln no Do not link to profile 2 when done
P1St Cont Continue profile operation when power is restored
P1Eb 8 Delay mode if temperature deviates ± 8°
P1r1 4.0 Ramp rate 1 is 4.0/minute
P1L1 350 Setpoint level 1 is 350
P1H1 20.0 Hold time 1 is 20.0 minutes
P1r2 3.0 Ramp rate 2 is 3.0/minute
P1L2 500 Setpoint level 2 is 500
P1H2 60.0 Hold time 2 is 60.0 minutes
P1r3 0.0 Ramp rate 3 is step ramp
P1L3 750 Setpoint level 3 is 750
P1H3 0.0 Hold time 3 is skipped
P1r4 7.5 Ramp rate 4 is 7.5/minute
P1L4 875 Setpoint Level 4 is 875
P1H4 150.0 Hold time 4 is 150.0 minutes
P1r5 10.0 Ramp rate 5 is 10.0/minute
P1L5 250 Setpoint level 5 is 250
P1H5 0.0 Hold time 5 is skipped
P1r6 3.8 Ramp rate 6 is 3.8/minute
P1L6 100 Setpoint level 6 is 100
P1H6 0.0 Hold time 6 is skipped
P1r7 -0.1 Ramp rate 7 ends profile
Profile Module 8 (8-Pr) (Cont’d)
Mnemonic Value Description
P1 1 1F2F Keep both outputs off
P1 2 1F2F Keep both outputs off
P1 3 1F2F Keep both outputs off
P1 4 1F2F Keep both outputs off
P1 5 1F2F Keep both outputs off
P1 6 1F2F Keep both outputs off
P1 7 1F2F Keep both outputs off
P1 8 1F2F Keep both outputs off
P1 9 1N2F Turn on auxiliary cooling
P110 1F2F Turn off auxiliary cooling
P111 1F2F Keep both outputs off
P112 1F2N Turn on end of profile signal
FACTORY SERVICE OPERATIONS MODULE (9-FS)
The Factory Service Operations are programming functions which are
performed on an infrequent basis. They include: controller calibration, and reset
programming to factory configuration setting. Given the ramifications of these
operations, access to each is protected by an access code number. Entering code
66 will restore all parameters to factory settings, the unit will indicate the
operation after the PAR button is pressed, by displaying “rSEt” in the lower
display momentarily. The calibration operations are detailed in Appendix “F”.
Note: Entering code 66 will reset all programming parameters to the
factory settings.