Display Parameter
Range and Units
(Factory Setting
Value)
Description/
Comments
CYC2 Cooling output
cycle time
0 to 120 sec
(2)
0 turns OP2 off.
GAN2 Relative cooling
gain
0.0 to 10.0
(1.0)
0.0 places cooling
output into ON/OFF
control mode and
db-2 becomes
hysteresis value,
db-2 Heating/cooling
overlap-deadband
-999 to 9999
(0)
Positive value is
deadband.
Negative value is
overlap. If GAN2 =
0, this parameter is
cooling ON/OFF
control hysteresis.
-53-
QUICK REFERENCE TABLE: CONFIGURATION COOLING MODULE 5 (5-O2)
Unit returns to configuration access point if cooling option not installed.
Comments to this Manuals