PROGRAM DIAGNOSTICS MENU (Cont’d)
TEST ALARMS
The up and down arrow keys are used to select an alarm output and set it to
the active or inactive state. This allows the user to check the operation of
devices wired to the alarm outputs and the wiring connections. Please note
that the active state is defined by the PHASE programming in the Program
Alarms Menu.
TEST DRIVE OUTPUT (TEST DRV OUT)
This function allows the user to test the Drive System. A % Output value is
entered through the front panel keypad causing the motor to run at the
corresponding speed. The display indicates the motor’s feedback frequency.
The Up and DN arrows set the percentage analog output. The percentage of
analog output is shown on line 1 of the display. The feedback frequency in Hz
is shown on line 2. Pressing F2/STP sets the % output to zero immediately.
Pressing ESC zeros the % output and exits to the previous menu.
Note: The F-STOP input must be held low or tied to common before a % output
value can be entered.
PROGRAM SECURITY MENU
This is used to select the PRO.CODE used for Program Mode access when
either the PGM.DIS. DIP switch is on or a User Input programmed for the
program disable function is active (see Front Panel Accessible
Programming). The value shown on the display is the current PRO. CODE.
The factory default value is 0. A new value may be entered in the range of 0 to
98. Entering a value of 99 will disable future entry into Programming Module
when the Program Disable DIP switch or a User Input terminal set for
Program Disable is active.
The following flowchart shows only the Security portion:
-30-